MTL SLP Surge Suppressor Unit

Unit Price189,29 EUR
Minimum Order Quantity1
Tariff No.
Lead Time
Weight and Dimension
DescriptionDepth12mm Dimensions105 x 12 x 86mm Height86mm Length105mm Maximum Operating Temperature+80°C Minimum Operating Temperature-40°C Product Details Ultra Slim Two Loop Protector Ultra-slim devices for protecting electronic equipment against surges on control loop cabling. Protection for two loops per SLP, or a single four-wire circuitATEX CertifiedMulti-stage hybrid protection circuitry Maximum rated load current 1.50A Loop resistance 2Ω Capacitance (Line - Line) 60pF Terminals 2.5mm (12 AWG) Mounting T-section DIN-rail Bandwidth (-3dB) 50MHz Surge Protection Devices, SPDs (DIN-rail) Voltage surges, often referred to as spikes or transients are typically caused by switching of fluorescent lights, fuses blowing or nearby lightning activity. The worst voltage surges are usually caused by lightning and can reach up to 6000V, with current surges of over 3000A. The maximum size of the voltage and current surges depends on the location within the building's wiring system. BS7671: 2011 Amendment 1 Sections 443 and 534 cover risk assessment and provides guidance on protection of electronic equipment for installation engineers to follow. The fullest information on lightning and surge protection comes from the BSEN 62305 series of standards.